詳細介紹
*6千伏電纜 YJV高壓電力電纜
適用范圍 Applications
本產(chǎn)品適用于工頻額定電壓3.6/6kv~26/35kv輸配電線路作配送電能子用。
The product is suitable for use in power transmission and distribution lines with rated power frequency voltage 3.6/6kv~26/35kv.
使用特性 Operating characteristics
· 工頻額定電壓U0/U為3.6/6kv~26/35kv。
Rated power-frepuency voltage U0/U: 3.6/6kv~26/35kv.
· 電纜導體的zui高允許工作溫度:90℃。
Max.admissible operating temperature of the conductor:90℃.
· 短路時(zui長時間不超過5s)電纜導體的zui高溫度不超過2500C。
Max. short-circurt temperature of conductor shall not exceed 2500C.
(5s maximum duration)
· 電纜敷設(shè)時環(huán)境溫度應不低于00C。
The ambient temperature under installation should not below 00C.
· 電纜彎曲半徑:三芯電纜不小于電纜外徑15倍;單芯電纜不小于電纜外徑20倍。
The bending radius of a single-core cable should not less than 20 times of the cable diameter.
The bending radius of a single-core cable should not less than 15 times of the cable diameter.
電纜額定電壓的選擇 Voltage designation
·*6千伏電纜 YJV高壓電力電纜
電纜的額定電壓應適合于電纜系統(tǒng)的運行狀況,用U0/U(Um)kv表示。
U0-電纜設(shè)計用的導體對地或金屬屏蔽之間的額定工頻電壓;
U-電纜設(shè)計用的導體間的額定工頻電壓;
Um-設(shè)備可承受的“zui高系統(tǒng)電壓”的zui大值。
The rated voltage of the cable for a given applixation shall be suitable for the operating conditions
in the system in which the cable is used,and is expressed in the form of U0/U(Um)kv
Where:
U0-The rated power-frequency voltage between conductors and earth metallic screen ,for which the cable designed;
U - The rated power-frequency voltage between conductos, for which the cable designed;
Um- The maximum value of the“highest system voltage”for which the equipment may beused.
如何防止電線電纜起火
1.保證施工質(zhì)量,特別是電纜頭的制作質(zhì)量一定要嚴格 符合規(guī)定要求。
2.加強電纜運行監(jiān)視,避免電纜過負荷運行。
3.按期進行電纜測試,發(fā)現(xiàn)不正常時應及時處理。
4.電纜溝要保持干燥,防止電纜受潮,造成絕緣下降,引起短路。
5.定期清掃電纜上所積粉塵,防止所積粉塵自燃引起電纜著火。
6.加強電纜回路開關(guān)及保護的定期校驗維護,保證其動作可靠。
7.電纜敷設(shè)時要保持與熱管路有足夠距離,控制電纜不小于0.5米;動力電纜不小于l米??刂齐娎|與動力電纜應分槽、分層并分開布置,不能層間重疊放置。對不符合規(guī)定的部位,電纜應采取阻燃、隔熱措施。
8.安裝火災報警裝置及時發(fā)現(xiàn)火情,防止電纜著火。
9.采取防火阻燃措施。